Eaton Firefighter's microphone for DAU500 PAVA system
The Firefighter's Microphone EF-FMWB is a wall-mounted microphone paging station, with the push-button panel and fireman microphone, for use with Eaton’s DAU500 voice alarm system. It can address up to 6 zones for emergency EVAC paging. It includes a fist microphone with built-in PTT button, which c
Request a quoteDescription
The Firefighter's Microphone EF-FMWB is a wall-mounted microphone paging station, with the push-button panel and fireman microphone, for use with Eaton’s DAU500 voice alarm system. It can address up to 6 zones for emergency EVAC paging. It includes a fist microphone with built-in PTT button, which can be pre-programmed to access a certain zone or group of zones. EVAC and ALERT messages may be triggered on the front of the panel by means of dedicated buttons. Additionally, the firefighter's microphone incorporates mandatory EN-54-16 system indications, as well as fault/emergency buzzer and mandatory manual controls, including Lamp Test and system reset. It is easily connected to L-Net interface of the public address and voice alarm system’s main DAU500 panel and can be daisy-chained with more L-Net devices.
Highlights
- Pre-programmable: Quickly communicate with a zone or zone group
- Compliant: Incorporates mandated EN-54-16 system indicators
- Secure: Robust wall unit secured with key
Unfamiliar building, emergency situation, would you know what to do?
Today, in a world where there are a growing array of threats such as fire, acts of terrorism and extreme weather, coupled with an increase in buildings with complicated layouts, the task of guiding people to safety in event of an emergency is more challenging than ever. With pre-recorded and live messaging given through public address and voice alarm systems the task is much easier and can potentially reduce evacuation time by 50%.
Product codes
- Firefighter's microphone, wall mounted | EF-FMWB
Product family: specifications and ordering options vary by model. Refer to the model details and official documentation.
Technical Specifications
| 24V (L-Net) | max. 180mA |
|---|---|
| Architecture | Master-slave, up to 16 slave devices per DAU500 panel |
| Audio processing | Fixed BP filter, fixed dynamics compression |
| Cabling | X-over FTP CAT5e (or higher) |
| Connection | RJ-45, powered daisy chain, digital audio & control data |
| Current rating via single link | max. 500 mA (up to 8 slave devices) via L-Net port, |
| Digital audio format | 24 kHz sampling, ADPCM compressed |
| Dimensions (HxWxD) | 38.5 x 44 x 13.5 cm |
| Evac manual control | EVAC message, ALERT message, SILENCE, RESET, fireman mic with PTT button |
| Fault indications | Power supply, system fault, network, zone fault |
| Fireman microphone | Integrated Fireman Mic with priority and electrical monitoring |
| Frequency response | 100 Hz – 12 kHz |
| General controls / indications | Lamp test button, silence button, power, evac, general fault LED indicators |
| Housing material | Steel / glass |
| IP rating | IP 44 |
| Manufacturer highlight: Compliant | Incorporates mandated EN-54-16 system indicators |
| Manufacturer highlight: Pre-programmable | Quickly communicate with a zone or zone group |
| Manufacturer highlight: Secure | Robust wall unit secured with key |
| Max. length of L-Net link | 250 m |
| Mounting | Wall-mounted, 4 x wall plug 6 x 60mm minimum |
| Number of zones | max. 6 zones (global network access) |
| Relative humidity | max. 90% (non condensing) |
| Storage temperature | -40–70°C |
| Temperature | 10–40°C |
| Weight | 6.2 kg |
| Zone controls / indications | 6 x configurable zone selection button, zone EVAC/FAULT/BUSY LED indicators |