Eaton DAU500 - All-in-one PAVA system
The DAU500 is all-in-one-box voice evacuation system. The wall mount panel contains a completely integrated voice evacuation system, capable of both standalone (for small systems) and network operation (for larger system expansion). It is certified in accordance with EN54-16 and EN54-4, which are ha
Request a quoteDescription
The DAU500 is all-in-one-box voice evacuation system. The wall mount panel contains a completely integrated voice evacuation system, capable of both standalone (for small systems) and network operation (for larger system expansion). It is certified in accordance with EN54-16 and EN54-4, which are harmonized standards under Construction Products Regulation, mandatory in the European Union. Powerful and flexible, DAU500 offers flexibility and optimisation for a range of voice applications large or small.
Highlights
- Versatile: Standalone or network operation
- Compliant: EN54-16 certified
- All-in-one: Integrated PAVA system in one panel
Emergency situation? Unfamiliar surrroundings? Get the message through!
The evacuation of a commercial building can be triggered by a growing array of potential threats, including fire, acts of terrorism or extreme weather. With the growing number of busy, complicated or unfamiliar buildings, the process of guiding people to safety is becoming increasingly complex. Public address and voice alarm (PAVA) systems are key to giving clear messages that guide individuals to safety, which is why they are an essential part in evacuation planning today.
Did you know voice alarm systems can reduce evacuation time by more than 50%?
Research from the British Standards Association (BSI), shows that those hearing a tone signal take more than six minutes to evacuate a building with which they are not familiar, while those hearing a recorded message will be out in around four minutes. Live announcements are even faster at less than two minutes.
Product codes
- DAU500 wall mount voice alarm system | EFDAU500
- Accessories: |
- Speaker line multiplexer | EF-HEXAPOD6
- 16 way Input/Output module | EF-GPIO-16WAY
- Multimode fiber module | EF-FSC-MM
- End of line module - 10 pack | EF-EOL-TL
- Replacement fire microphone | EF-FMP
- 1 x 100v Transformer standard | EF-T100
- 1 x 70v Transformer switchable | EF-T107
- Terminal box | EF-HTB
- Terminal box with window | EF-HTB-W
Technical specifications
- Number of zones | max. 6 local zones
- Maximum total loudspeaker load | 600 W RMS (420W RMS pure sinewave according to EN54-16)
- Power amplifiers | 6 x 100 W, modular (2 channels per module), bridgeable up to 3 x 200 W. Note: Line voltage dependant upon transformer used.
- Standby power amplifiers | 2 x 100 W / 1 x 200 W dedicated backup amplifiers
- Loudspeaker line monitoring |
- Built-in | 20 kHz AC monitoring with EOL module, short/open/impedance deviation
- Loudspeaker type | with 70 V/100 V step-down transformer
- Voice messages |
- Storage | max. 22 audio files x 5 minutes each, micro-SD card with content monitoring
- Message player | max. 2 simultaneous local message playback
- Controls and indications |
- General controls / indications | Lamp test button, silence button, power, evac, general fault LED indicators
- Fault indications | Power supply, system fault, network, zone fault
- Zone controls / indications | 6 x configurable zone selection button, zone EVAC/FAULT/BUSY LED indicators
- Evac manual control | EVAC message, ALERT message, SILENCE, RESET, fireman mic with PTT button
- Fireman microphone | Integrated Fireman Mic with priority and electrical monitoring
- Power supply equipment | Built-in power supply system, EN 54-4 certified.
- AC supply | 110 – 230 V AC, 50/60Hz
- AC current consumption | max. 5.3A @115 V AC / 2.65 A @230V AC
- Inrush current | 20 A @115 V AC, 40 A @230 V AC
- Power supply protection | Overload current limiting, over voltage shutdown, over temperature shutdown.
- Battery requirements |
- Type | Sealed, rechargeable lead-acid battery for stationary use
- Capacity | 10 – 55 Ah
- Charging time (80% capacity) | < 24 h
- Rated voltage | 24 V DC (2 x 12V)
- Battery dimensions | 2 batteries, each of max. 230 x 138 x 207 mm (LxWxH) (not supplied)
- Battery weight | max. total 32.6 kg
- Inputs |
- 2 x BGM | 2 x independent balanced analogue in, line-level mono, 22 kΩ input impedance
- 6 x EVAC in, 1 x SILENCE in, 1 x RESET in | monitored logic inputs, 4.7 kΩ + 10 kΩ EOL resistors
- 8 x GPI | unmonitored logic inputs (pull-down, configurable active low/hi)
- Outputs |
- EVAC out, FAULT out | Potential-free relay output (configurable NO/NC)
- GPO | 8 x Open collector output (configurable NO/NC) max. max 24 vDC/110mA
- Loudspeaker out | 6 x 100 V transformer output, 20 kHz AC monitoring with EOL
- Amplifiers |
- Type | Class D
- Protection | over load shut down, over temperature shut down
- Backup amplifiers | 2 dedicated backup channels, auto backup at end stage failure, auto restore
- Efficiency | 80% @ rated power
- Output voltage | max. 100 V RMS or 70 V RMS (according to transformer setting)
- Rated power | max 100 W per channel
- Output bandwidth | 50 Hz – 20 kHz
- SNR | >80 dB
- THD + N | 0.1% @ rated power
- Networking |
- Max. number of devices in the network | 254
- Max. number of zones | 254
- Max. total system output power | 152 kW
- Number of simultaneous network audio | 2
- Network audio transmission latency | 0.3 ms per device
- Local network |
- Architecture | Master-slave, up to 16 slave devices per DAU500 main unit
- Connection | 3 x L-Net port, RJ-45, powered daisy chain, digital audio & control data
- Cabling | X-over FTP CAT5e (or higher)
- Current consumption | max. 500 mA (up to 8 slave devices) per L-Net port
- Max. length of local bus: |
- default | 250 m
- Global network |
- Architecture | Peer-to-peer, up to 254 x DAU500 main units
- Connection | 2 x G-Net port, RJ-45, powered redundant ring, digital audio & control data
- Cabling | X-over FTP CAT5e (or higher) / multimode optical fiber
- Current consumption | max. 500 mA per port, reserved only for fiber extenders
- Max. distance between devices: |
- default | 250 m
- with fiber extenders | 2500 m (2km on fiber, 2 x 250m copper)
- Audio performance and mechanical details
- Audio |
- Frequency response: |
- Local BGM | 50 Hz – 20 kHz
- Messages, network streaming | 100 Hz – 12 kHz
- Analog input- output latency | < 10 ms (stand-alone system)
- Network audio stream format | 24 kHz sampling, ADPCM compressed
- Message file input format | 24 kHz, 16 bit, mono WAV
- DSP features | HP/LP filter, multipoint parametric EQ
- Mechanical |
- Dimensions (HxWxD) | 80 x 52 x 28 cm
- Weight (full config, without batteries) | 29 kg
- Housing material | Steel / ABS
- IP rating | IP30
- Mounting | Wall-mounted box
Product family: specifications and ordering options vary by model. Refer to the model details and official documentation.
Technical Specifications
| Manufacturer highlight: All-in-one | Integrated PAVA system in one panel |
|---|---|
| Manufacturer highlight: Compliant | EN54-16 certified |
| Manufacturer highlight: Versatile | Standalone or network operation |
Documents & Technical Downloads
Eaton Fire Training Calendar 2026
Catalogues
Voice Alarm and Refuge Systems - Product Catalogue
Catalogues · en
EFDAU500 Distributed amplifier unit - Product specification
Product specification guides
Fire systems - Compatibility guide
Product specification guides · en
EF-HTB/EF-HTB-W Terminal box for EFDAU500 - Datasheet
Technical data sheets
EF-VVCS Voice View Control Station Software for DAU500 - Datasheet
Technical data sheets
EFDAU500 Distributed amplifier unit - Datasheet
Technical data sheets
Fire system and devices - Extended warranty-policy and terms