Context Plus ZFP RS485 Multipath network interface PCB
• The Context Plus ZHN allows the interconnection of up to 64 Context Plus ZFP Main Panels (any mix) and up to 64 ZFP Compact Controllers over a two-wire RS485 ring-wired, multi-path, fault-tolerant ‘Hi-Net’ network. • One ZHN required per ZFP Main Panel (ZFP Compact Controllers model ZREP1S include
Request a quoteDescription
Type: RS485.
Indicators: Network Status LEDs.
Connections: From node to node, connect A (IN) to A (OUT), B (IN) to B (OUT) and C (IN) to C (OUT). Terminals A and B are for data comms and terminal C is for earth screens.
Network specification: Multi-path, fault-tolerant RS485. Max. 126 network nodes (up to 64 ZFP mains & 64 Compact Controllers); Max. cable length of network: 128km; Max. cable length between nodes: 1km. For standard non-fault tolerant network specs see main instructions.
Notes: Each node requires a unique ID number (1-126) which is set via Dip switch (SW1)
on the ZHN PCB.
Sales Leaflet
View LeafletTechnical Specifications
| Connections | From node to node, connect A (IN) to A (OUT), B (IN) to B (OUT) and C (IN) to C (OUT). Terminals A and B are for data comms and terminal C is for earth screens. |
|---|---|
| Indicators | Network Status LEDs. |
| Type | RS485. |