Addressable Manual Call Points
Apollo SA5900-903APO Intelligent Manual Call Point – White
Apollo·SKU: SA5900-903APO
The Manual Call Point is commonly used to manually initiate a hazard alert.
Request a quoteDescription
The Manual Call Point is commonly used to manually initiate a hazard alert.
- Resettable operating element
- 170° viewable LED
- Suitable for semi flush or surface mounting
- ‘Plug and Play’ terminal connections for faster wiring
- Continuity link for wiring test before commissioning
- XP95, Discovery and CoreProtocol compatible
Technical Specifications
| Conformance - Standards | EN 54-11, EN 54-17 |
|---|---|
| Electrical - Maximum power-up time | 1 second |
| Electrical - Polarity | L1 &, L2 are polarity sensitive |
| Electrical - Power-up surge current | 1mA |
| Electrical - Protocol voltage | 5 to 13V peak to peak |
| Electrical - Protocol voltage (max) | 13V |
| Electrical - Protocol voltage (min) | 5V |
| Electrical - Quiescent current | 100μA |
| Electrical - Quiescent current tested at | 24V dc |
| Electrical - Status indicator – Alarm | Red |
| Electrical - Status indicator – Fault | Yellow |
| Electrical - Status indicator – Isolate | Yellow |
| Electrical - Status indicator – Poll | Flashing green |
| Electrical - Supply voltage (max) | 35V dc |
| Electrical - Supply voltage (min) | 17V dc |
| Electrical - Supply voltage (Vmin-Vmax) | 17 to 35V dc |
| Environmental - Humidity | 0% to 95% (no condensation or icing) |
| Environmental - Humidity (max) | 95%, RH |
| Environmental - Humidity (min) | 0%, RH |
| Environmental - Humidity Note | no condensation or icing |
| Environmental - IP rating Value | IP44 |
| Environmental - Operating temperature | -40 to 70°C / -40 to 158°F |
| Environmental - Operating temperature (max) | 70°C / 158°F |
| Environmental - Operating temperature (min) | -40°C / -40°F |
| General - Warranty | 10 year |
| Mechanical - Colour | White |
| Mechanical - Key type | Apollo, Manal, Call, Point reset key |
| Mechanical - Materials housing | Polycarbonate |
| Mechanical - Product depth | 63mm / 2.48in |
| Mechanical - Product length | 90mm / 3.54in |
| Mechanical - Product width | 90mm / 3.54in |
| Mechanical - Weight | 180g |
| Performance - Action | Single |
| Performance - Alarm level analogue value | 64 |
| Performance - Analogue value nominal | 16 |
| Performance - Fault level analogue value | 4 |
| Performance - Operating element | Resettable element |
| Performance - Type | A |
Documents & Technical Downloads
PP2526_Intelligent MCP_Issue 4.pdf
Datasheet
PP2090 Short-Circuit Isolation Datasheet
Datasheet
Intelligent Manual Call Point BIM Files
BIM
Intelligent Manual Call Point BIM Files
BIM
Intelligent Manual Call Point Installation Guide
Guide
DoC – EMC Directive 2014//30/EU_RoHS Directive 2011/65/EU_2015/863/EU
Certificate
Related Products
View Cataloguearrow_forward
Simplex 4090-9005 (IDNET Release Peripheral)
Indicative Price
from

Addressable Manual Call Point – Glass Element
Indicative Price
from

Addressable Manual Call Point with Built-in Isolator – Glass Element
Indicative Price
from

Addressable Manual Call Point with Built-in Isolator – Glass Element
Indicative Price
from