Apollo 55000-588APO XP95 Input/Output Module – Three Channel – Isolating (Obsolete)
The XP95 Input/Output Module – Three Channel – Isolating is used to control and monitor the operation of a circuit of conventional sounders or bells.
Request a quoteDescription
This product is now obsolete.
The XP95 Input/Output Module – Three Channel – Isolating is used to control and monitor the operation of a circuit of conventional sounders or bells.
- EN 54-17 & EN 54-18 Certified
- Allows independent monitoring of input channels
- Allows independent control of output relays
- XP95, Discovery compatible
Technical Specifications
| Conformance - Approvals | CPR, VdS, LPCB |
|---|---|
| Electrical - Maximum cable resistance | 50Ω |
| Electrical - Maximum continuous current | 1A |
| Electrical - Maximum power-up time | 150ms |
| Electrical - Maximum switching current | 3A |
| Electrical - On resistance | 0.2Ω |
| Electrical - Power-up surge current | 6.5mA |
| Electrical - Protocol voltage | 5 to 9V peak to peak |
| Electrical - Protocol voltage (max) | 9V |
| Electrical - Protocol voltage (min) | 5V |
| Electrical - Quiescent current, 20kΩ EOL fitted | 3mA |
| Electrical - Supply voltage (max) | 28V dc |
| Electrical - Supply voltage (min) | 17V dc |
| Electrical - Supply voltage (Vmin-Vmax) | 17 to 28V dc |
| Electrical - Switch input monitoring voltage | 9 to 11V dc |
| Electrical - Switch input monitoring voltage (max) | 11V dc |
| Electrical - Switch input monitoring voltage (min) | 9V dc |
| Environmental - Humidity | 0% to 95% (no condensation or icing) |
| Environmental - Humidity (max) | 95%, RH |
| Environmental - Humidity (min) | 0%, RH |
| Environmental - Humidity Note | no condensation or icing |
| Environmental - IP rating Value | IP54 |
| Environmental - Operating temperature | -20 to 70°C / -4 to 158°F |
| Environmental - Operating temperature (max) | 70°C / 158°F |
| Environmental - Operating temperature (min) | -20°C / -4°F |
| General - Warranty | 10 year |
| Manufacturer status | Obsolete |
| Mechanical - Colour | White |
| Mechanical - Relay output contact rating | 1A |
| Mechanical - Relay output rating tested at | 30V ac |
Documents & Technical Downloads
PP2121 Three Channel Input Output Module Datasheet
Datasheet
PP2090 Short-Circuit Isolation Datasheet
Datasheet
Three Channel Input/Output Unit BIM Files
BIM
Three Channel Input/Output Unit BIM Files
BIM
Three Channel Input/Output Unit Installation Guide
Guide
CPR – Certificate of Constancy of Performance
Certificate
VdS – Verband der Schadenversicherer
Certificate
CPR -UKCA Certificate of Constancy of Performance
Certificate
LPCB – Loss Prevention Certification Board Certificate
Certificate
DoP – Declaration of Performance
Certificate
DE – DoP - Declaration of Performance
Certificate
DoP – UKCA Declaration of Performance
Certificate
EMC Directive 2014//30/EU_RoHS Directive 2011/65/EU_2015/863/EU
Certificate
Related Products
View Cataloguearrow_forward
Edwards SIGA-IOI FG, Module, Input/Output;SIGA-IOI
Indicative Price
from
Edwards 4-AUDTELS-E Audio and Telephone Interface/Riser Module, Europe, Edwards
Indicative Price
from