ANSUL Inert Gas System 300 (IGS-300)
300 Bar Gaseous Clean Agent Fire Suppression System
Request a quoteDescription
300 Bar Gaseous Clean Agent Fire Suppression System The ANSUL IGS-300’s engineering design leverages a 300-bar system with either 80L or 140L containers. This can significantly reduce the footprint when compared to 200-bar systems or systems limited to using 80L containers. The strategic combination of high-pressure technology and higher-capacity containers offers several key benefits, particularly in environments where space constraints are a concern. In addition to enhanced regulated flow technology, ANSUL IGS-300 uses clean agents INERGEN® or IG-55 to effectively help extinguish fires with reduced discharge turbulence, helping avoid the risk of damage to sensitive equipment or materials.
Technical Specifications
| Feature 1 | UL/ULC Listed, FM Approved |
|---|---|
| Feature 2 | Removable pressure gauge is UL Listed, FM Approved |
| Feature 3 | Matrix bracket technology for design flexibility of container footprint |
| Feature 4 | Can be designed in accordance with NFPA 2001, EN 15004 & ISO 14520 |
| Feature 5 | Master container actuation feature can operate up to 84 subordinate containers – no pilot container required |
| Feature 6 | Integrates INERGEN acoustic nozzles, which attenuates sound when discharged to protect sound-sensitive equipment |
Documents & Technical Downloads
Ansul Inert Gas System 300 Brochure ( English )
Brochure · English
Data Center Fire Protection Brochure (F-2025010) ( English )
Brochure · English
Gem Inert Gas System 300 Brochure (FS2410021) ( English )
Brochure · English
Ansul Inert Gas Acoustic Nozzle Data Sheet (F-2016267) ( English )
Datasheet · English