Fire Alarm Power Supply Units
Altronix AL802ULADAJ NAC Power Extender
Altronix·SKU: AL802ULADAJ
Indicative Price
Excluding local taxes and shipping.
NAC POWER EXTENDER - 24VDC OR 12VDC AT 8 AMP. 2 - CLASS A OR 4 - CLASS B NAC CIRCUITS, OPERATES 2-WIRE HORN/STROBES, GE Model AL802ULADAJ is an extremely cost effective 8 amp voltage regulated remote power supply/battery charger. It may be connected to any 24 volt Fire Alarm Control Panel (FACP). Pr
infoNo online payment — request a quote and our team sends pricing. Prices are indicative and exclude taxes & shipping.
Description
NAC POWER EXTENDER - 24VDC OR 12VDC AT 8 AMP. 2 - CLASS A OR 4 - CLASS B NAC CIRCUITS, OPERATES 2-WIRE HORN/STROBES, GE
Model AL802ULADAJ is an extremely cost effective 8 amp voltage regulated remote power supply/battery charger. It may be connected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support system accessories. The unit delivers regulated and filtered 24 volt power to Class B or Class A NAC loop circuits. Additionally, a separate 1.0A auxiliary output with reset for four (4)-wire smoke detectors is available. The 8 amp rated supply current can be divided between the four (4) outputs for powering NAC devices. Each output is rated at 2.5 amp max., and can be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may be programmed for Input to Output Follower Mode (output will follow input. i.e. March Time Input, March Time Output). An individual output of 4 amp is achieved by paralleling 2 outputs. In non-alarm condition independent loop supervision for Class A and/or Class B FACP NAC circuits is provided. In the event of a loop trouble the FACP will be notified via the steered input (input 1 or input 2). In addition, there are common trouble output terminals (NC, C, NO) which are used to indicate general loop/system trouble. A common trouble input is provided for optional NC (normally closed) devices to report trouble to the FACP. Two (2) FACP signaling outputs can be employed and directed to control supervision and power delivery to any combination of the four (4) outputs. The unit also features "Loop Output" trouble memory indication to help identify troublesome sporatic problems.
UPC: 782239936854
Also known as: AX-802ULADJ, ALT-AL802ULADAJ
Technical Specifications:
|
Technical Specifications
| Brand | Altronix |
|---|---|
| Compatibility | Fire Alarm SystemsNotification Appliance Circuits |
| Depth | 4.6" |
| Depth (mm) | 117.475 |
| Environmental Certification | RoHS |
| Environmentally Friendly | Yes |
| Form Factor | Wall Mount |
| Height | 18" |
| Height (mm) | 457.2 |
| Input Voltage | 110 V AC |
| Input Voltage (V AC) | 110 |
| Limited Warranty | Lifetime |
| Manufacturer Part Number | AL802ULADAJ |
| Product Type | Proprietary Power Supply |
| UPC | 782239936854 |
| Weight (Approximate) | 10.70 lb |
| Weight (Approximate) (g) | 4853.438 |
| Width | 14.5" |
| Width (mm) | 368.3 |